Acrel AKH-0.66/I Series Current Transformer

Acrel AKH-0.66/I Series Current Transformer

 

● Clamshell design

● Beautiful shape easy wiring

● High accuracy

● Suitable for busbar or cable

Certificate: CE

微信图片_20241113104505_副本微信图片_20241113104458_副本


Product Detail

Technical Parameters

Download

Product Tags

Acrel AKH-0.66/I Series Current Transformer

General

Acrel AKH-0.66/I Series Current Transformer can be used together with measuring instruments by collecting AC current signals. The measuring range of primary current is 15-3000A, and the secondary output is 5A or 1A. The measuring range is 5-120% of the rated value. Clamshell design, beautiful appearance, convenient wiring. The cover material is transparent polycarbonate, which can clearly see the secondary lead wiring. Square and square combination of holes, both through the cable, or through the busbar.

Acrel AKH-0.66/I Series Current Transformer can be used together with measuring instruments by collecting AC current signals.

Diagram of AKH-0.66/I Series Current Transformer

Spec. and size akh-0.66-i-series-current-transformer
Type Outline size Through size Mounting size Tolerance
(mm)
W H D a e Φ M N
30I 60 78 36 31 11 22 34 57.5 ±1
40I 75 95 45 40 11 31 40 57.5
60I 102 130 45 61.5 21 45 42 57.5
80I 118 140 45 82 11 52 60 57.5

 

AKH-0.66/I Series Current Transformer can be installed in three ways: A-type straight plate is fixed, B-type bent plate is fixed, and C-type single plate pressure plate is fixed. Note that when the current transformer is in use, the secondary open circuit shall not be allowed, and the secondary outlet S2 shall be grounded.

diagram-of-akh-0.66-i-series-current-transformer

Benefits of AKH-0.66/I Series Current Transformer

 Clamshell design easy to view wiring

• Beautiful shape easy wiring

• High accurancy with CE standard

 Suitable for busbar or cable

Use of AKH-0.66/I Series Current Transformer

• Used for internal measurement in industrial and mining enterprises

• Measure a busbar or cable in the power distribution room

• Convert the large current at the primary side to 5A or 1A, connect to energy meter

• When using a current transformer, the secondary open circuit is not allowed, and the secondary outlet S2 should be grounded


  • Previous:
  • Next:

  • Acrel AKH-0.66/I Series Current Transformer

    Technical Parameters

    Shape Specification Rated current ratio (A) Rated current ratio (A) Straight- through tums Bus spec(mm)/number Max cable outer diameter (mm) Installation
    0.2
    0.5
    1
     30I_副本 30I 15/5(1) 1.5
    5
    / Ф22 A
    20/5(1) 1.5
    4
    25-30/5(1) 1.5
    3
    40-60/5(1) 1.5
    2
    75-100/5(1) 1.5
    1
    30×10/1 A、B
    150-200/5(1) 2.5
    250/5(1) 3.75
    300-450/5(1) 5
    500/5(1) 10
    600/5 10
    40I_副本 40I 10/5(1) 1.5
    10
    / Ф30 A
    15/5(1) 1.5
    8
    20/5(1) 1.5
    5
    25-30/5(1) 1.5
    4
    40/5(1) 1.5 3
    50-75/5(1) 1.5
    2
    100/5(1) 1.5
    1
    40×10/1 A、C
    150/5(1) 2.5
    1
    200/5(1) 2.5
    1
    250/5(1) 3.75 1
    300-450/5(1) 5 1
    500-800/5(1) 10 1
    1000/5(1) 10 1
    60I_副本 60I 150/5(1) 2.5 1 60×10/160×6/1-2 Ф44 A、C
    200-250/5(1) 2.5 1
    300-450/5(1) 5 1
    500-800/5(1) 10 1
    1000-1250/5(1) 10 1
    1500-2000/5(1) 20 1
    2500/5(1) 30 1
     80I_副本 80I 150/5(1) 2.5 1 80×10/1 Ф50 A、C
    200-250/5(1) 2.5 1
    300-400/5(1) 5 1
    500-800/5(1) 10 1
    1000-1250/5(1) 10 1
    1500-2000/5(1) 20 1
    2500-3000/5(1) 30 1

     

     

     