Acrel AKH-0.66/P Protection Current Transformer
Acrel AKH-0.66/P Protection Current Transformer
General
Acrel AKH0.66-P is mainly suitable for the relay protection circuit that multiple busbars pass through. This product is developed for the protection system to detect short circuit or overload current. It has different accuracy levels and accuracy limit coefficients, and can be expanded to different perforation sizes. It is widely used in low-voltage power distribution. The protection system, power plant and industrial and mining enterprise circuits can be used in conjunction with our ARD3T motor protector unit and ALP circuit protection, and can also be used in conjunction with ABB's SPAJ140C relay.
Diagram of AKH-0.66/P Protection Current Transformer
Type / Size | |||||||||
Outline size
|
Through size
|
Mounting size
|
Figure
|
Tolerance
|
|||||
W | H | D | a | e | M | N | |||
P-60Ⅲ
|
117 | 147 | 55 | 52 | 62 | 60 | 70.5 |
Fig.1
|
±1
|
P-80Ⅲ
|
117 | 167 | 55 | 52 | 82 | 60 | 70.5 |
Fig.1
|
|
P-100Ⅲ
|
120 | 190 | 55 | 52 | 102 | 60 | 70.5 |
Fig.1
|
|
P-130Ⅲ
|
125 | 224 | 55 | 52 | 132 | 60 | 70.5 |
Fig.1
|
|
P-60×50II
|
112 | 177 | 70 | 62 | 52 | 60 |
/
|
Fig. 2
|
|
P-80×50II
|
132 | 177 | 70 | 82 | 52 | 80 |
/
|
Fig. 2
|
|
P-100×50II
|
190 | 177 | 70 | 102 | 52 | 139 |
/
|
Fig. 2
|
|
P-130×50II
|
220 | 177 | 75 | 131 | 51 | 170 |
/
|
Fig. 2
|
|
P-170×100II
|
227 | 230 | 60 | 172 | 105 | 103 | 83 |
Fig. 2
|
|
P-180×50II
|
239 | 181 | 60 | 185 | 55 | 40 | 83 |
Fig. 2
|
|
P-220×50II
|
280 | 190 | 60 | 225 | 55 |
65/55/65
|
83 |
Fig. 2
|
Installation of Acrel AKH-0.66/P Protection Current Transformer

Wiring of AKH-0.66/P Protection Current Transformer

Acrel AKH-0.66/P Protection Current Transformer
Technical Parameters
Picture | Specification | Rated current ratio (A) | Accuracy degree and corresponding rated load(VA) |
Straight-
through
tums
|
Bus
spec(mm)
/
number
|
Installation
|
||
5P5
|
5P10
|
5P15
|
||||||
P-60Ⅲ
|
200-250/5(1)
|
5 | / |
/
|
1 |
60×10/
1-3
|
E | |
300-500/5(1)
|
5 | 2.5 |
/
|
1 | ||||
600-1500/5(1)
|
10 | 5 | 2.5 | 1 | ||||
P-80Ⅲ
|
500-600/5(1) | 5 | 2.5 |
/
|
1 |
80×10/
1-3
|
||
700-1250/5(1)
|
10 | 5 |
/
|
1 | ||||
1500/5(1)
|
10 | 5 | 2.5 | 1 | ||||
2000-3000/5(1)
|
15 | 10 | 2.5 | 1 | ||||
P-100Ⅲ
|
600/5(1)
|
5 | 2.5 |
/
|
1 |
100×10/
1-3
|
||
700-1250/5(1)
|
10 | 5 |
/
|
1 | ||||
1500/5(1)
|
10 | 5 | 2.5 | 1 | ||||
2000-3000/5(1)
|
15 | 10 | 2.5 | 1 | ||||
P-130Ⅲ
|
1000/5(1) | 15 | 10 | 2.5 | 1 |
130×10/1-3
125×10/1-3
|
||
1200-1250/5(1)
|
15 | 10 | 5 | 1 | ||||
1500-2000/5(1)
|
20 | 10 | 5 | 1 | ||||
2500-3000/5(1)
|
30 | 15 | 5 | 1 | ||||
4000-5000/5(1)
|
30 | 15 | 2.5 | 1 |
Picture | Specification | Rated current ratio (A) | Accuracy degree and corresponding rated load(VA) |
Straight-
through
tums
|
Bus
spec(mm)
/
number
|
Installation | |||
5P5 | 5P10 | 5P15 | 5P20 | ||||||
P-170×100II
|
1000/5(1)
|
10 | 2.5 | 1 |
/
|
1 |
160×10/1-3
80×10/3-6
|
D | |
1250-2500/5(1)
|
15 | 5 | 1 |
/
|
1 | ||||
3000/5(1)
|
20 | 5 | 1 |
/
|
1 | ||||
4000-5000/5(1)
|
30 | 10 | 1 |
/
|
1 | ||||
P-180×50II
|
1000-2000/5(1)
|
15 | 10 | 5 |
/
|
1 |
180×10/1-3
80×10/3-6
|
||
2500-3000/5(1)
|
20 | 10 | 5 |
/
|
1 | ||||
4000-5000/5(1)
|
30 | 15 | 1 |
/
|
1 | ||||
P-220×50II
|
1000/5(1)
|
15 | 10 | 2.5 |
/
|
1 |
220×10/1-3
100×10/1-6
|
||
1250-2000/5(1)
|
15 | 10 | 5 |
/
|
1 | ||||
2500-3000/5(1)
|
20 | 10 | 5 | 2.5 | 1 | ||||
4000-6300/5(1)
|
30 | 15 | 10 | 5 | 1 |
AKH-0.66 CT and Hall Effect Sensor CE-LVD Certificate AT78251SC205023