Acrel AKH-0.66/P Protection Current Transformer

Acrel AKH-0.66/P Protection Current Transformer

 

•Current transformer for Protection

•10P5 10P10 10P15

Certificate: CE

微信图片_20241113104505_副本微信图片_20241113104458_副本


Product Detail

Technical Parameters

Download

Product Tags

Acrel AKH-0.66/P Protection Current Transformer

General

Acrel AKH0.66-P is mainly suitable for the relay protection circuit that multiple busbars pass through. This product is developed for the protection system to detect short circuit or overload current. It has different accuracy levels and accuracy limit coefficients, and can be expanded to different perforation sizes. It is widely used in low-voltage power distribution. The protection system, power plant and industrial and mining enterprise circuits can be used in conjunction with our ARD3T motor protector unit and ALP circuit protection, and can also be used in conjunction with ABB's SPAJ140C relay.

Diagram of AKH-0.66/P Protection Current Transformer

Type / Size
AKH-0.66 P protection current transformer dimension - 1AKH-0.66 P protection current transformer dimension - 2
Outline size
Through size
Mounting size
Figure
Tolerance
W H D a e M N
P-60Ⅲ
117 147 55 52 62 60 70.5
Fig.1
±1
P-80Ⅲ
117 167 55 52 82 60 70.5
Fig.1
P-100Ⅲ
120 190 55 52 102 60 70.5
Fig.1
P-130Ⅲ
125 224 55 52 132 60 70.5
Fig.1
P-60×50II
112 177 70 62 52 60
/
Fig. 2
P-80×50II
132 177 70 82 52 80
/
Fig. 2
P-100×50II
190 177 70 102 52 139
/
Fig. 2
P-130×50II
220 177 75 131 51 170
/
Fig. 2
P-170×100II
227 230 60 172 105 103 83
Fig. 2
P-180×50II
239 181 60 185 55 40 83
Fig. 2
P-220×50II
280 190 60 225 55
65/55/65
83
Fig. 2

 

Installation of Acrel AKH-0.66/P Protection Current Transformer

AKH-0.66 P protection current transformer installation

Wiring of AKH-0.66/P Protection Current Transformer

AKH-0.66 P protection current transformer wiring_副本

  • Previous:
  • Next:

  • Acrel AKH-0.66/P Protection Current Transformer

    Technical Parameters

    Picture Specification Rated current ratio (A) Accuracy degree and corresponding rated load(VA)
    Straight-
    through
    tums
    Bus
    spec(mm)
    /
    number
    Installation
    5P5
    5P10
    5P15
    AKH-0.66 P protection current transformer - 1_副本
    P-60Ⅲ
    200-250/5(1)
    5 /
    /
    1
    60×10/
    1-3
    E
    300-500/5(1)
    5 2.5
    /
    1
    600-1500/5(1)
    10 5 2.5 1
    P-80Ⅲ
    500-600/5(1) 5 2.5
    /
    1
    80×10/
    1-3
    700-1250/5(1)
    10 5
    /
    1
    1500/5(1)
    10 5 2.5 1
    2000-3000/5(1)
    15 10 2.5 1
     AKH-0.66 P protection current transformer - 2_副本
    P-100Ⅲ
    600/5(1)
     5 2.5
    /
    1
    100×10/
    1-3
    700-1250/5(1)
    10 5
    /
    1
    1500/5(1)
    10 5 2.5 1
    2000-3000/5(1)
    15 10 2.5 1
    P-130Ⅲ
    1000/5(1) 15 10 2.5 1
    130×10/1-3
    125×10/1-3
    1200-1250/5(1)
    15 10 5 1
    1500-2000/5(1)
    20 10 5 1
    2500-3000/5(1)
    30 15 5 1
    4000-5000/5(1)
    30 15 2.5 1

     

    Picture Specification Rated current ratio (A) Accuracy degree and corresponding rated load(VA)
    Straight-
    through
    tums
    Bus
    spec(mm)
    /
    number
    Installation
    5P5 5P10 5P15 5P20
    AKH-0.66 P protection current transformer - 3_副本
    P-60×50II
    100/5(1)
    2.5 /
    /
    / 1
    60×10/
    1-3
    D
    150/5(1)
    2.5 1.5
    /
    / 1
    200/5(1)
    5 1.5 / / 1
    300/5(1)
    5 2.5
    /
    /
    1
    400/5(1)
    10 2.5 /
    /
    1
    500-800/5(1)
    10 5 2.5 / 1
    1000-2000/5(1)
    15 10 5 2.5 1
    P-80×50II
    200-300/5(1)
    5 2.5 / / 1
    80×10/
    1-3
    400-600/5(1)
    10 5 2.5
    /
    1
    1000/5(1)
    15 10 5
    /
    800-2000/5(1)
    15 10 5 2.5 1
    2500/5(1)
    20 15 10 5 1
     AKH-0.66 P protection current transformer - 4_副本
    P-100×50II
    600-800/5(1)
    10 5 2.5
    /
    1
    100×10/
    1-3
    1000-1500/5(1)
    15 10 5 2.5 1
    2000-4000/5(1)
    20 15 10 5 1
    P-130×50II
    600-800/5(1)
    10 5 2.5
    /
    1
    120×10/
    1-3
    125×10/
    1-3
    130×10/
    1-3
    1000-1250/5(1) 15 10 5 2.5 1
    1500/5(1) 20 15 5 2.5 1
    2000-2500/5(1) 20 15 10 5 1
    3000-5000/5(1) 30 15 10 5 1

     

    Picture Specification Rated current ratio (A) Accuracy degree and corresponding rated load(VA)
    Straight-
    through
    tums
    Bus
    spec(mm)
    /
    number
    Installation
    5P5 5P10 5P15 5P20
     AKH-0.66 P protection current transformer - 5_副本
    P-170×100II
    1000/5(1)
    10 2.5 1
    /
    1
    160×10/1-3
    80×10/3-6
    D
    1250-2500/5(1)
    15 5 1
    /
    1
    3000/5(1)
    20 5 1
    /
    1
    4000-5000/5(1)
    30 10 1
    /
    1
    P-180×50II
    1000-2000/5(1)
    15 10 5
    /
    1
    180×10/1-3
    80×10/3-6
    2500-3000/5(1)
    20 10 5
    /
    1
    4000-5000/5(1)
    30 15 1
    /
    1
    P-220×50II
    1000/5(1)
    15 10 2.5
    /
    1
    220×10/1-3
    100×10/1-6
    1250-2000/5(1)
    15 10 5
    /
    1
    2500-3000/5(1)
    20 10 5 2.5 1
    4000-6300/5(1)
    30 15 10 5 1

    AKH-0.66 CT and Hall Effect Sensor CE-LVD Certificate AT78251SC205023

    CE证书-PD_0478_2024