Acrel BR Series Rogowski Coil Current Transformer
Acrel BR Series Rogowski Coil Current Transformer
General
Acrel BR series flexible Rogowski coil is a high-sensitivity flexible current sensor that can be directly integrated with portable devices such as power analyzers. It is suitable for energy consumption monitoring, high-frequency current monitoring, DC ripple measurement, and more. Customizable in different sizes upon request.
Dimension of BR Series Rogowski Coil Current Transformer
| Model Name | Inner Diameter | Sector Diameter | Circumference | 
| BR-90 | 90mm | 12mm | 300mm | 
| BR-150 | 150mm | 12mm | 500mm | 
| BR-200 | 200mm | 12mm | 650mm | 
| BR-300 | 300mm | 12mm | 1000mm | 
		    
			Installation of BR Series Rogowski Coil Current Transformer
		    
			Noted: Before installing the Rogowski CT on monitoring circuits, first you need to wire the Rogowski CT with paired energy meter.
		    
			Noted: The clamping up installation direction of CT must be according to the actual forward current direction. [Normally consider the direction from source to loads as forward current direction]
Acrel BR Series Rogowski Coil Current Transformer
Technical Parameters
| Model | 
 BR-90 
 | 
 BR-150 
 | 
 BR-200 
 | 
 BR-300 
 | 
| Circumferense | 300mm | 500mm | 650mm | 1000mm | 
| 
 Inner Diameter 
 | 
90mm | 150mm | 200mm | 300mm | 
| 
 Rated Current 
 | 
1000A | 
 2000-5000A 
 | 
 4000-8000A 
 | 
 5000-10000A 
 | 
| Sector Diameter | 
 12mm 
 | 
|||
| 
 Output Cable Length 
 | 
 Default 2m, Output Cable Length 
other size customizable 
 | 
|||
| 
 Ratio 
 | 
 200±0.5%mV/kA@50Hz 
Other Specs customizable 
 | 
|||
| 
 Positional Error 
 | 
 ±1% 
 | 
|||
| 
 OA Output 
[Zero Drift] 
 | 
 ≤1mV 
 | 
|||
| 
 Phase Angle Error 
 | 
 ≤0.5° 
 | 
|||
| 
 Linearity 
 | 
 ±0.2% 
 | 
|||
| 
 Bandwidth 
 | 
 1Hz – 10kHz 
 | 
|||
| 
 Operating Temp. 
 | 
 -40℃ – 80℃ 
 | 
|||
| 
 Storage Temp. 
 | 
 -50℃ – 90℃ 
 | 
|||
| 
 Flame Retardant 
 | 
 Thermoplastic rubber for wires and cables 
IEC-60332-1-2 compliant 
 | 
|||
| 
 Shielding 
 | 
 100% for coil, 100% for signal cable 
 | 
|||
| Insulation Voltage | 
 Coil: 3000V; Signal cable: 300V 
 | 
|||
            