Acrel DJSF1352-RN-2 Din Rail DC Energy Meter
Acrel DJSF1352-RN-2 Din Rail DC Energy Meter
General
Acre DJSF1352-RN-2 rail-mounted DC energy meter is designed mainly for DC charging piles, telecommunication base stations, solar photovoltaic and other application occasions. This series of instruments can measure voltage, current, power and positive and negative energy in the DC system. The test results can be used for local display and can also be connected with industrial control equipment and computers to form a measurement and control system.
Functions

Accuracy
Class 0.5
Pulse output
One channel power pulse output, 1-9999imp/kWH
Communication
RS 485 Modbus-RTU,DL/T 645-2007,DLT698
Power Supply:
AC/DC 85-265V or DC12V-48V
Dimension(L*W*H):
36*70*90 mm
Temperature:
Normal operating temperature:-25℃~+65℃
Storage temperature:-40℃~+80℃

Front Panel

Wiring
Terminals and wiring

Shunt input

Positive current input

Negative current input
Hall Sensor input

0-5V Input

0-200mA Input
Note:
1. When the negative current shunt is input, the option needs to be set to on in the instrument menu. See Section 6 Menu Programming Interface for details. If it is not set, the voltage value will be negative.
2.It is recommended to use 0.75mm2 or 1mm2 shielded twisted pair for the secondary weak signal line of voltage and current input, and the shielding layer needs to be connected to the ground.
Network

Applications
• Suitable for Solar PV Power Distribution Monitoring Solution
• Measure electric parameters of dc batterys
• Power consumption monitoring of DC charging pile
• DC monitor system of telecom tower base station
Outline and Dimension

Adopt standard DIN35mm rail installation
Acrel DJSF1352-RN-2 Din Rail DC Energy Meter
Technical Parameters
Technical parameters
|
Index | ||
Input
|
Nominal value
|
Voltage input range
|
Current input
|
DC 0-100V、DC 0-1000V
See the physical wiring diagram
|
Shunt:0-75mV
Hall sensor: 0-5V,0-200mA
|
||
Overload
|
1.2 times can sustain normal operation, 2 times can sustain 1 second
|
||
Power consumption
|
Voltage:≤0.2VA,Current≤0.1VA
|
||
Accuracy level
|
0.5 Class
|
||
Function
|
Display
|
Dot matrix LCD
|
|
Communication interface
|
RS485
|
||
Communication Protocol
|
Modbus-RTU,DL/T 645-2007,DLT698
|
||
Pulse output
|
One channel power pulse output
|
||
See the display in SYS->PLUS in the instrument menu setting, for example:
display 100, which means 100imp/kWH
|
|||
Working
power supply
|
Voltage range
|
AC/DC 85-265V or DC12V-48V(Auxiliary power supply code P1)
|
|
Power consumption
|
≤ 6W
|
||
Power frequency withstand voltage
|
Power supply//signal input//RS485 communication 4kV/1min;
Except for power supply, signal input and RS485 communication, other unconnected circuits 2kV/1min
|
||
Insulation resistance
|
≥ 40M Ω
|
||
Average barrier-free working time
|
≥50000h
|
||
Environment
|
Temperature
|
Normal operating temperature:-25℃~+65℃
Storage temperature:-40℃~+80℃
|
|
Humidity
|
≤95%RH, No condensation, no corrosive gas
|
||
Altitude
|
≤3000m
|