Acrel ADL400W Three Phase CT Operated Din Rail Energy Meter Built-in Wifi Communication

Acrel ADL400W Three Phase CT Operated Din Rail Energy Meter Built-in Wifi Communication

●Three-phase: 3×230/400V

●Accessory: 0.5

●DIN 35 mm

 


Product Detail

Technical Parameters

Product Tags

Acrel ADL400W Three Phase CT Operated Din Rail Energy Meter Built-in Wifi Communication

General

ADL200W ADL400W Series DIN-Rail Mounted Multifunctional and Dual Circuits Electric Energy Meter With External Current Transformer is an intelligent instrument mainly designed for new energy power generation systems such as photovoltaic grid-connected system, micro inverter system, energy storage system, AC coupling system, etc. The product has the advantages of high precision, small volume, high respondent speed and convenient installation. It can monitor and measure real-time power and other power parameters, support protocols such as Modbus-TCP and http, and communicate with inverters or energy management systems (EMS) via Wi-Fi or Lora communication to achieve functions such as anti-reverse flow, regulating power generation, and battery charging and discharging. It can be bidirectionally measured to achieve energy management for household distributed photovoltaic systems.

Wiring

ADL200W ADL400W Diagram of Voltage and Current Connection
ADL200W 400W - 2

Outline and Dimension

ADL200W ADL400W dimension
ADL200W ADL400W CT dimension

Application for Balcony PV System

ADL200W 400W - 3
ADL200W 400W - 1

  • Previous:
  • Next:

  • Acrel ADL400W Three Phase CT Operated Din Rail Energy Meter Built-in Wifi Communication

    Functions

    Function Descriptions
    Electric energy metering Active energy metering (forward and reverse)
    Reactive energy metering (forward and reverse)
    Split-phase energy
    Electric quantity measurement U, I
    P, Q, S, PF, F
    Communication RS485 、Wi-Fi 、Lora

     

     Technical Parameters
    Item Performance Parameters
    Model Series ADL200W ADL400W
     

     

     

    Measurement

    Grid Single-phase Three-phase four-wire
    Voltage (Unom) Nominal voltage 230V 3×230/400V
    Input Range 0.8Unom ~ 1.2Unom
    Overload 1.2 times rating (continuous) 22 times the rating for 1 second
    Power consumption <2w,    <10VA
    Accuracy class Error ±0.5%
    Current Minimum current (Imin) 0.3A
    Transitional current (Itr) 1.5A
    Basic current (Ib) 30A
    Maxinum current (Imax) D16Imax = 120A
    Short-term overcurrent 30 times the maximum current for 20ms
    Power consumption <1W,    <1VA
    Accuracy class Error ±0.5%
    Power Active, reactive, apparent power, error ±1.0℅
    Grid frequency 50Hz, error ±0.5%
    Response rate 50ms (voltage, current, power)
    Installation category CAT III
    overvoltage level OVC III
    Metering Active electric energy Class 1or B
    electromagnetic compatibility E2
    Security Power frequency withstand voltage Between communication and signal input, AC3kV 1min
    Insulation resistance Input and output terminals to casing >100MΩ
    Communication RS485 interface Modbus RTU protocol; addr:1~ 247;Baud rate:1200bps-38400bps
    Wi-Fi Protocols: Modbus-TCP, Http, etc. Operating frequencyband: 2.4GHz
     

     

    Environment

    Operating temperature range -25℃~+55℃
    Operating temperature range -40℃~+70℃
    Storage temperature -40℃~+85℃
    Relative humidity ≤95% (without condensation)”Not suitable for damp environments”
    海拔高度Altitude ≤2000m
    IP rating IP20 on terminal strip without protective housing and IP51 in protective housing, per IEC 60529
    Pollution Degree II
    UC Degree III
    Installation environment Indoor use
    Protect Degree Class II (Double Insulation)
    usage environment Cabinet mounted(The outer shell cannot be touched)
    usage environment M1
    Transformer Safetycharacteristics Insulation resistance: greater than 1000 MΩ under normal conditions;
    Electric strength resistance: It can withstand 4000V, 50Hz power frequency for 1 minute;Flame retardancy: Conforms to UL94-V0 level;
     

     

     

     

    Reference standard

    EN IEC 61010-1:2010 Safety requirements for electrical  equipment for measurement, control, and laboratory use - Part 1: General requirements

    EN IEC 61010-2-030:2010 Safety requirements for

    electrical equipment for measurement, control, and

    laboratory use - Part 2-030: Particular requirements for equipment having testing or measuring circuits

    EN IEC 61326-1:2021 Electrical equipment for   measurement, control, and laboratory use - EMC requirements – Part 1: General requirements

    EN IEC 61326-2-1:2021 Electrical equipment for

    measurement, control, and laboratory use - EMC

    requirements – Part 2-1: Particular requirements for

    electromagnetic compatibility testing for electrical

    equipment for measurement, control, and laboratory use

    EN 50470-3 Electricity metering equipment (a.c.) - Part 3: Particular requirements - Static meters for active energy

    (class indexes A, B and C)