Acrel DJSF1352-RN-6 Din Rail DC Energy Meter

Acrel DJSF1352-RN-6 Din Rail DC Energy Meter

 

• Voltage input range: DC 0-100V, DC 0-1500V

• Current input: Shunt: 0-75mV, Hall sensor: 0-5V, 0-200mA

• Accuracy level: 0.5 class

• Display: 8-bit segment LCD screen (LCD)

• Communication interface: RS485 (two options)

• Communication protocol: Modbus RTU, DL/T 645-2007, DLT698

• Working power supply: AC/DC 85–265 V or DC 12–48 V

• 6P size


Product Detail

Technical Parameters

Product Tags

Acrel DJSF1352-RN-6 Din Rail DC Energy Meter

General

Acre DJSF1352-RN-2 rail-mounted DC energy meter is primarily designed for DC charging stations, telecommunications base stations, photovoltaic systems, and other applications. This series of devices measures voltage, current, power, and positive and negative energy in the DC power system. The measurement results can be displayed locally and connected to industrial control devices and computers to form a measurement and control system.

Functions

DJSF1352-RN-6 - 6

Accuracy

Class 0.5

Pulse output

Two channels power pulse output, 1-9999imp/kWH

Communication

RS 485 Modbus-RTU,DL/T 645-2007,DLT698

 

Power Supply:

AC/DC 85-265V or DC12V-48V

Dimension(L*W*H):

108*70*94 mm

Temperature:

Normal operating temperature:-25℃~+65℃

Storage temperature:-40℃~+80℃

DJSF1352-RN-6 - 7

Front Panel

DJSF1352-RN-6 - 3

Wiring

Terminals and wiring

DJSF1352-RN-6 - wiring

Shunt and Hall sensor input

DJSF1352-RN-6 - wiring2

Network

ADW300 - network - 2_副本

Applications

• Suitable for Solar PV Power Distribution Monitoring Solution

• Measure electric parameters of dc batterys

• Power consumption monitoring of DC charging pile

• DC monitor system of telecom tower base station

Outline and Dimension

DJSF1352-RN-6 - outline
DJSF1352-RN-6 - dimension

  • Previous:
  • Next:

  • Acrel DJSF1352-RN-6 Din Rail DC Energy Meter

    Technical Parameters

    Technical parameters
     Index
    Input
    Nominal value
    Voltage input range
    Current input
    DC 0-100V、DC 0-1500V
    See the physical wiring diagram
    Shunt: 0-75mV
    Hall sensor: 0-5V, 0-200mA
    Overload
    1.2 times can sustain normal operation, 2 times can sustain 1 second
    Power consumption
    Voltage: ≤0.2VA, current ≤0.1VA
    Accuracy class
    Class 0.5
    Function
    Display
    8-bit segment LCD screen (LCD)
    Communication Interface
    RS485(two options)
    Communication protocol
    Modbus-RTU,DL/T 645-2007,DLT698
    Switch
    Switch output (DO)
    2 relay outputs, 2A/30VDC or 2A/250VAC
    Switch input (DI)
    2 dry contact inputs
    Analog
    Analog output (AO)
    4-20mA output (0.5 level)
    Pulse output
    Two-way power pulse output (the second power pulse can be switched to second pulse)
    See the display in SYS->PULS in the meter menu setting, for example: display 100, which means 100imp/ kWH
    Working
    power
    supply
    Voltage
    AC/DC 85-265V or DC 12V-48V
    Power consumption
    ≤10W
    Power frequency
    withstand voltage
    Power supply//signal input//RS485 communication 4kV/1min;
    Except for power supply, signal input and RS485 communication, other unconnected circuits are 2kV/1min
    Insulation resistance
    ≥100MΩ
    Average barrier-free
    working time
    ≥50000h
    Environment
    Temperature
    Working temperature: -25℃~+65℃
    Storage temperature: -40℃~+80℃
    Humidity
    ≤95%RH, no condensation, no corrosive gas
    Altitude