Acrel AIM-T500 Industrial Insulation Monitoring Device
Acrel AIM-T500 Industrial Insulation Monitoring Device
General
Acrel Industrial insulation monitoring device is mainly used to monitor the insulation status of the IT system (ungrounded system) to the ground, and timely alarm when the system has insulation fault to remind the electrical maintenance personnel to check the fault. It is suitable for AC and DC ungrounded systems in industrial fields such as electrolytic aluminum, mines, glass factories, electric furnaces and test equipment, metallurgical plants, chemical plants, explosion-hazardous places, computer centers and emergency power supplies.
Panel Specification

LCD Display

Typical Connection

Benefits of AIM-T500 Industrial Insulation Monitoring Device
• LCD display with backlit
• Unearthed AC, DC main circuits
• IT systems including high leakage capacitances
• Coupled IT systems
Application of Industrial IT Isolated Power System?
Industrial IT isolated power system is specially developed by ACREL for IT power distribution systems in industrial occasions such as mines, glass plants, electric furnaces and test equipment, ships, metallurgical plants, chemical plants, explosion-hazardous places, computer centers and emergency power supplies. The system has rich functions, including insulation resistance monitoring, insulation fault early warning, insulation fault alarm, event recording, parameter setting, communication networking, etc. When the system has a ground fault, it can alarm in time, and accurately locate the specific circuit where the fault occurs, so as to Remind the relevant personnel to troubleshoot the fault in time.
Acrel Industrial IT Isolated Power System FAQs
Acrel AIM-T500 Industrial Insulation Monitoring Device
Technical Parameters
Auxiliary Power Supply | Frequency | 40-60Hz |
Power Consumption | <8W | |
Voltage Range | System Voltage | AC/DC 0~480V |
Communication | Interface | RS485 |
Protocol | MODBUS-RTU |
Type | AIM-T500 | AIM-T300 | |
Accessory power supply | AC 85~265V; DC100~300V; 50/60Hz | AC 85~265V; DC100~300V; 50/60Hz | |
Power dissipation | < 8W | < 6W | |
System voltage | AC 0~690V; DC 0~800V; 40~460Hz | AC 0~480V; DC 0~480V; 40~460Hz | |
System application | IT system (online), Other system (offline) | IT system (online), Other system (offline) | |
Insulation monitoring | Measuring range | 1k~10MΩ | 1k~5MΩ |
Alarm range | 10k~10MΩ | 10k~5MΩ | |
Resistance accuracy | 1~10k,1k; 10k~10M, ±10% | 1~10k, 1k; 10k~5M, ±10% | |
system leakage capacitance | <500μF | <150μF | |
Response time (Ce=1μF) | <5s | <6s | |
Internal parameters | Measuring voltage | <50V | <20V |
Measuring current | <270μA | <170μA | |
Internal DC impedance | ≥180kΩ | ≥120kΩ | |
Relay output | Error, Alarm, Warning | Warning, Alarm | |
SOE | 20 records (fault type, fault value, fault time) | 20 records (fault type, fault value, fault time) | |
Alarm type | LCD, LED indicator | LCD, LED indicator | |
Communication | RS485, Modbus-RTU | RS485, Modbus-RTU | |
Impulse voltage / Pollution Level | 8kV/Ⅲ | 8kV/Ⅲ | |
EMC/ Radiation | IEC61326-2-4 | IEC61326-2-4 | |
Environment | Working temperature | -10 ~+65℃ | -10 ~+65℃ |
Storage temperature | -20~+70℃ | -20~+70℃ | |
Relative humidity | <95%, without condensation | <95%, without condensation | |
Altitude | ≤2500m | ≤2500m |
1. Manual for Acrel AIM-T500 Industrial Insulation Monitoring Device
2. Installation and Use for Acrel AIM-T500 Industrial Insulation Monitoring Device
3. Debugging Software for Acrel AIM-T500 Industrial Insulation Monitoring Device