Acrel AMC16Z-FDK24 DC Multi Circuits Energy Meter

Acrel AMC16Z-FDK24 DC Multi Circuits Energy Meter

 

● Designed specifically for the power supply management of server in the data center

● A+B independent 12 circuits(24 in total)

● U, I, P, Q, S, PF, kWh, kvarh

● 2nd-31st  Harmonic

● kWh Class 0.5

● DIN 35 mm


Product Detail

Technical Parameters

Product Tags

Acrel AMC16Z-FDK24 DC Multi Circuits Energy Meter

General

AMC16Z series DC precise distribution monitoring device is a measurement device designed specifically for data center server power management.The device design exquisite, can for A + B two into line and 96 road for electrical parameters, the input and output parameters of the switch state and the lightning protection device such as real-time monitoring, all alarm threshold measurement channels can be set in A separate, to qualify the limit event trigger system sound and light alarm, immediately on the volume in the traditional instrument, the height of the monitoring circuit integration.

Functions

AMC16Z-FDK24 4802

12 channels of each circuit of A+B

 

independent 2 circuits the outgoing current

 

active power, active power, reactive power

 

2-31st harmonic, 48DI

 

1 RS485 communication

Installation:

DIN rail 35mm

 

Work temperature: 

 -15℃ ~ 55℃

 

Dimension (L*W*H):

180*94.3*45mm

 

 Auxiliary Power Supply:

DC 12V/24V

AMC16Z-FDK24 4804

Front Panel

AMC16Z-FAK24 front panel

①first channel current input

②first channel voltage input

③RS485

④DC12V/24V Power input

⑤Second channel current input

⑥Second channel voltage input

Application of AMC16Z-FDK24 DC Multi Circuits Energy Meter

ZMC16Z-ZD - wiring - 1
AMC16Z-KA - typical connection - 2
AMC16Z-KA - typical connection - 3

Wiring

AMC16Z-ZD - wiring - 1

Typical Connection

AMC16Z-KA - typical connection

①AMC16Z-FAK24/48 Measure 24/48 channels of each circuit of A+B out line

②AMC16Z-ZA  Measure A+B independent 2 circuits three-phase main into line

③RS485 communication line

④AKH-0.66W Type ct or AKH-0.66-EMS type (50,100,200400A)/50mA

⑤AKH-0.66/30I Tpye ct

⑥ATP007kt 7-inch Touch screen or ATP010kt 10-inch Touch screen

On-site Picture

AMC16Z-ZA - application - 1_副本
AMC16Z-ZA - application - 2_副本
AMC16Z-ZA - application - 4

Packaging

Packaging Overview(Minimum) amc16z-za-ac-multi-channel-energy-meter8 amc16z-za-ac-multi-channel-energy-meter9 amc16z-za-ac-multi-channel-energy-meter10 amc16z-za-ac-multi-channel-energy-meter11
Packing Dimension and Weight(Minimum) Package dimensions(1 PC)

220*170*90mm

Package Weight(1 PC)

0.35Kg

Packing Dimension and Weight(Large) Package dimensions(24 PC)

615*480*395mm

Package Weight(24PC)8.4Kg
Average Lead Time Manufacturing: 3~4 days(If paired with system need extra 1~2 days for adjustment) Shipment: 8~9 days(World Wide Shipment)
Product HS Code   9028301400
Country of Origin China

  • Previous:
  • Next:

  • Acrel AMC16Z-FDK24 DC Multi Circuits Energy Meter

    Product Models

    AMC16Z-ZD(-P24)
    Monitor the full power parameters of the A+B dual DC incoming circuit, monitor the status of 6 switches,
    2 alarm outputs, 1 temperature and humidity detection, 1 RS485 communication, ±12V output
    (Only power supply to incoming module matching Hall sensor), DC24V independent auxiliary power supply.
    AMC16Z-FD
    Monitor the full power parameters of 24 branches of A+B dual-channel DC outlet, and 1 channel of RS485 communication.
    AMC16Z-FDK24
    Monitor the full power parameters and switch status of the 24 branches of the A+B dual DC out going line, and 1 channel of RS485 communication.
    AMC16Z-FDK48
    Monitor the full power parameters and switch status of the 48 shunts of the A+B dual DC outgoing lines, and 1 channel of RS485 communication.
    AMC16Z-KA
    Wet contact, monitoring A+B total 48 branch switch state, 1-way RS485 communication.
    AMC16Z-KD
    Dry contact, monitoring A+B total 48 branch switch state, 1-way RS485 communication.
    AMC16Z-AC220V
    AC220V extended power supply, and use when the monitoring circuit is beyond 96 branches of A+B

    Technical Parameters

    Technical parameters
    AMC16Z-FDK24
    AMC16Z-FDK48
    Measurement parameters
    Voltage, current, power, energy, switching status
    Bus voltage
    Rated
    48VDC,240VDC,336VDC
    Measuring range
    ±20%
    Overload
    Instantaneous voltage 2x/sec
    Current outgoing loop
    Rated
    5V (Hall sensor, external supply required ±12V)
    Range
    Overload
    Lasts 1.2x, instantaneous 10x/sec
    Measurement accuracy
    Outlet
    Voltage/current 0.5 level, power/energy level 1
    Auxiliary power supply
    Powered by AMC16Z-ZD, DC 12-24V when used alone
    Environment
    Temperature
    Working: -15°C~55°C Storage: -25°C~ 70°C
    Humidity
    Relative humidity ≤ 93%
    Altitude
    ≤2500m
    Communication
    RS485/Modbus-RTU
    Installation method
    DIN35mm rail or baseplate mounting
    Protection level
    IP20
    Pollution level
    2
    Security
    Insulation
    The insulation resistance between all terminals and the conductive parts of the housing is not less than 100MΩ
    Withstand
    pressure
    A voltage and current signal B voltage and currentsignal between the other ports meet AC2kV 1min, leakage current should be less than 2mA, no breakdown or flashover phenomenon
    Electromagnetic both
    Capacities
    Anti-static
    interference
    Level 4
    Resistant to RF
    electromagnetic
    field radiation
    Level 3
    Note: The AMC16Z-FDK module has a secondary side input voltage of 5V and a primary-side current default of 50A. If the Hall sensor is different, the customer can set the ratio through the touch screen according to the actual use.