Acrel BM100-DI Signal Isolator

Acrel BM100-DI Signal Isolator

● Input: 0~20mA /4~20mA

● Output: 0~20mA /4~20mA (Safe side input); Load resistance: ≤550Ω

● Powered 20~35V DC

● 35mm Din rail installation


Product Detail

Technical Parameters

Product Tags

Acrel BM100-DI Signal Isolator

General

Acrel BM100 series signal isolators can measure the electrical parameters such as current and voltage or non-electrical parameters such as temperature and resistance at high speed and accurately, and can be converted into standard analog signal output after the isolation device. It can be directly connected with pointer meter and digital display meter, and can also be connected with automatic control instrument (such as PLC), various A/D converters and computer systems. It is widely used in electric power, railway, petrochemical, metallurgy, chemical industry, food, warehousing and other industries.

Features

BM100 Series Signal Isolator-3

① DC voltage/current input

② Using magnetic isolation technology

③ Load resistance: ≤550Ω

④ TS35 rail installation

⑤ Powered 20~35V DC

Types

BM100 Series Signal Isolator-types

Wiring

BM100-DI/I-B11
BM100-DII B11 wiring
BM100-DI/□-C12
BM100 DI C12 wiring
BM100-DI/□-C22
BM100 DI C22 wiring

Outline and Dimension

BM100-□□/□-B□□
BM100-Isolated-Safety-Barrier-dimension-1
BM100-□□/□-C□□
BM100-Isolated-Safety-Barrier-dimension-2

Structure

BM200 Isolated Safety Barrier - structure - 1

Application

BM series signal isolator application - 1

Date Center

BM series signal isolator application - 2

Building

BM series signal isolator application - 3

Industrial Automation

BM series signal isolator application - 4

Seaport


  • Previous:
  • Next:

  • Acrel BM100-DI Signal Isolator

    Technical Parameters

    Channel type Single-way input and single-way output,single-way input and double-way output,

    double-way input and double-way output

    Input type Current/Voltage/Thermal resistance Pt100/Resistance
     

    Input signal

    DC 0~20mA /4~20mADC 0~5V /1~5V /0~ 10V

    Pt100(Minimum range: 50℃)

    0~ 10KΩ(Minimum range: 1KΩ)

     

    Output signal

    DC 0~20mA /4~20mA ; Load resistance: ≤550ΩDC 0~5V /1~5V; Load resistance: ≥330KΩ

    Load resistance: ≥30KΩ(Pt100/Resistance input)

    DC 0~ 10V /2~ 10V; Load resistance: ≥500KΩ

    Load resistance: ≥30KΩ(Pt100/Resistance input)

    Transmission accuracy 0.2%
    Temperature modulus 50ppm/℃ (Voltage output: 100ppm/℃)
    Response time 5ms to reach 90% of final value(RTD Pt100/resistance input: 1s to reach 90% of final value)
    Power supply 20~35V DC or 85~265VAC/DC
    Work temperature -20℃~+60℃
    Fix mode Rail installation
    Dielectric strength ≥1500VAC/1 min (Among input//output//power supply)

    Note: Input distribution voltage of two wire input and three wire input≥14V (when 20mA input)