Acrel ADW600 Multi Circuits Power Metering Module
Acrel ADW600 Multi Circuits Power Metering Module
General
Acrel ADW600 is an advanced IoT multi-circuit power metering module for modern low-voltage power distribution systems. Capable of three-phase energy monitoring, it accurately measures voltage, current, power and energy consumption of multiple circuits. Featuring a modular structure including voltage, current, relay output, temperature measurement and leakage current modules interconnected via Ethernet, it supports flexible module combinations. Compact and easy to install, it delivers high-precision metering alongside diverse communication interfaces. Powered by IoT architecture, it enables real-time data transmission, remote management and data analysis.
Widely deployed in EV charging stations, data centers, commercial buildings and power distribution facilities, it fits multi-circuit metering scenarios and low-voltage grid power renovation projects. Offering comprehensive energy data and operational visibility, the ADW600 helps users boost energy efficiency, cut operational costs and strengthen power system safety, serving as a dependable choice for next-gen smart energy monitoring and IoT power management.
Application Scenario
Wiring Diagram
Outline and Dimension
Acrel ADW600 Multi Circuits Power Metering Module
Functions
|
Model |
Function |
|
ADW600-M |
Data collection and remote transmission (4G / Ethernet / WIFI) |
|
ADW600-U |
Voltage measurement and sampling |
|
ADW600-I |
Active power metering (positive and reverse), Quadrant reactive power energy |
|
Voltage, current, power factor, frequency, active power, reactive power, apparent power |
|
|
Total harmonic content, sub-harmonic content (2nd to 31st) |
|
|
Pulse Output of active energy |
|
|
ADW600-K |
4DI、2DO |
|
ADW600-TL |
12 channels of temperature measurement, 4 channels of residual current measurement |
Technical Parameters
| ADW600-U | Rated Voltage | 3×57.7/100V,3×220/380V,3×100V, 3×380V |
| Voltage Accuracy | 0.5% | |
| Frequency | 45-65Hz | |
| Power Consumption | <0.5VA (each phase) | |
| ADW600-I | Input Current | D10:0.03-0.15(6)A,D16:0.8-2(100)A,D24:3.2-8(400)A,D36:4.8-12(600)A |
| Accuracy of Active Energy | B Class | |
| Pulse width of energy | 80±20ms | |
| Active Energy Pulse Constant | D10:6400imp/kWh,D16:400imp/kWh,D24:100imp/kWh,D36:60imp/kWh | |
| Power Consumption | <1VA (each phase) | |
| ADW600-K | DI | 4-channel passive input, built-in DC12V power supply |
| DO | 2-channel passive output, capacity AC230V/DC30V, 3A | |
| ADW600-TL | Temperature Measurement | 12-channel temperature measurement, accuracy:±2℃, with 12 temperature measurement leads. |
| Residual Current Measurement | 4-channel residual current measurement, input range up to 1mA, accuracy 1%, residual current transformer must be purchased separately |
| Temperature Range | Operating temperature |
-25℃~55℃Storage temperature-40℃~70℃Humidity≤95%
(without condensation)Altitude<2000m